Basic protection for two-core systems with HF applications 120 V
产品简介
Basic protection for two-core systems with HF applications 120 V
产品详细信息
Basic protection for measuring, control and regulation technology and telecommunication systems.
• Basic protection for lightning protection equipotential bonding
• High impulse arresting capacity 6 kA (10/350)
• With easy-to-mount, screwless connection terminals
• In a space-saving 17.5 mm grid
Application: Universal use on 35 mm hat profile rails in standard distributor housings.
| Type |
Maximum continuous operating voltage Vc/AC V |
Maximum continuous voltage Vc/DC V |
Number of poles | Connection system |
Pack. pcs |
Weight kg/100 pcs. |
Art.-No. | Add to item list |
| TKS-B | 120 | 170 | 2 | Terminal | 1 | 4.400 | 5097976 |
|
| /pc. |
Download Datasheet (PDF)
| Article number | 5097976 | ||
| Maximum continuous operating voltage Vc/AC | V | 120 | |
| Maximum continuous voltage Vc/DC | V | 170 | |
| Lightning protection Zone LPZ | 0?3 | ||
| Number of poles | 2 | ||
| Rated current | IL | A | 20 |
| Serial impedance per path | ? | - | |
| Impulse durability line-earth | C2: 18 kV / 9 kA | ||
| Total Impulse durability (10/350) | kA | D1: 6 | |
| Total arrestor peak current (8/20) | kA | 18 | |
| Voltage protection level line-line | V | 950 | |
| Voltage protection level line-earth | V | 600 | |
| Shielding connection available | No | ||
| Shield connection | - | ||
| Temperature range | ? | °C | -40 - +80 |
| Division unit TE (17.5 mm) | 1 | ||
| Connection cross-section, flexible | mm² | 0.14 - 2.5 | |
| Connection cross-section, multi-wire | mm² | 0.14 - 2.5 | |
| Connection cross-section, rigid | mm² | 0.14 - 2.5 | |
| Testing standard | IEC 61643-21 |