Photovoltaic housing 600 V DC with connection terminals with IR
产品简介
Photovoltaic housing 600 V DC with connection terminals with IR
产品详细信息
System solution for photovoltaic systems with connection terminals and remote signalling
• Error-resistant Y circuit for use according to VDE 0100-712 (IEC 60364-7-712)
• Low DC protection level: < 3.0 kV (Voc max = 900 V DC with V25-B+C/0-450PV)
• Low DC protection level: < 2.6 kV (Voc max = 600 V DC with V50-B+C/0-300PV)
• 5 parallel connection terminals up to 6 mm² for each polarity (+ and –)
• Pre-mounted in IP65 housing
Note: 5 PV strings can be switched in parallel on the terminals. The technical data (string voltage, etc.) and the conditions of the converter (number of MPP trackers) must be taken into account.
Additional measures may be necessary if there is the risk of condensation formation.
| Type |
U max DC V |
Version | Art.-No. | Add to item list |
| VG-BC DC-MSFS600 | 600 | Type 1+2 with FS in housing with terminals | 5088695 |
|
| VG-BC DC-MSFS900 | 900 | Type 1+2 with FS in housing with terminals | 5088696 |
|
| /pc. |
Download Datasheet (PDF)
| Article number | 5088695 | 5088696 | ||
| U max DC | Uc DC | V | 600 | 900 |
| SPD to EN 61643-11 | Type 1+2 | Type 1+2 | ||
| Lightning protection Zone LPZ | 0?2 | 0?2 | ||
| Impulse discharge current (10/350) | Iimp | kA | 12,5 | 7 |
| Nominal discharge current (8/20) | In | kA | 30 | 30 |
| Maximum discharge current | Imax | kA | 50 | 60 |
| Voltage protection level | Up | kV | < 2,6 | < 3,0 |
| Response time | tA | ns | < 25 | < 25 |
| Connection cross-section, rigid | mm² | 0.5 - 6 | 0.5 - 6 | |
| Connection cross-section, flexible | mm² | 0.5 - 6 | 0.5 - 6 | |
| Temperature range | ? | °C | -40 - +80 | -40 - +80 |
| Protection rating | IP 65 | IP 65 |