Protection set MCD + V20 3-pole + NPE with remote signalling
产品简介
Protection set MCD + V20 3-pole + NPE with remote signalling
产品详细信息
Series PS...: Protection Set,, Type 1+2 (Class B+C) lightning and surge arrestor to VDE 0675 Part 6-11 (DIN EN 61643-11).
• Arresting capacity 100 kA 10/350 µs BET tested
• Pre-mounted and ready for connection, including connecting bridges, connection terminals marked
• With remote signalling, potential-free NO contact, for function monitoring
• For use in TN-C network system
Note: Max. backup fuse (required only if not already fitted in network) 125 A gL/gG.
| Type |
Max. continuous operating voltage V |
Version |
Pack. pcs |
Weight kg/100 pcs. |
Art.-No. | Add to item list |
| PS4-B+C TNS+FS | 255 | 3 + NPE | 1 | 211.000 | 5089763 |
|
| /pc. |
Download Datasheet (PDF)
| Article number | 5089763 | ||
| Nominal voltage | UN | V | 230 |
| SPD to EN 61643-11 | Type 1+2 | ||
| SPD to IEC 61643-11 | class I+II | ||
| Lightning protection Zone LPZ | 0?2 | ||
| Impulse discharge current (10/350) | Iimp | kA | 100 |
| Total discharge current (10/350) | ITotal 8/20 | kA | 100 |
| Nominal discharge current (8/20) | In | kA | 100 |
| Arrestor surge current (8/20) [total] | ITotal 8/20 | kA | 100 |
| Maximum discharge current | Imax | kA | 100 |
| Voltage protection level | Up | kV | <1,3 |
| Response time | tA | ns | <25 |
| Follow current interrupt rating | Ifi | kA | 25 |
| Maximum back-up fuse | A | 125 | |
| Temperature range | ? | °C | -40 - +85 |
| Division unit TE (17.5 mm) | 11 | ||
| Connection cross-section, rigid | mm² | 10 - 50 | |
| Connection cross-section, multi-wire | mm² | 10 - 35 | |
| Connection cross-section, flexible | mm² | 10 - 25 |