实用型 耐压/绝缘测试仪 Extech 7112
产品简介
停产...
产品详细信息
MODEL | 7112 | ||
AC WITHSTANDVOLTAGE | |||
Output Rating | 5KVAC/12mA | ||
Range | Resolution | Accuracy | |
Output Voltage,KVAC | 0-5.00 | 0.01 | ±(2% of setting +5V) |
Output Frequency | 50Hz/60Hz ±100ppm, UserSelection | ||
Output Waveform | Sine Wave ,THD.<2%(Resistive Load), Crest Factor = 1.3 - 1.5 | ||
Output Regulation | ± (1% of output + 5V), From noload to full load | ||
SETTINGS | |||
Hi-Limit AC Current,mA | 0.10 - 12.00 | 0.01 | ±(2% of setting +2counts) |
Lo-Limit AC Current,mA | 0.00 - 12.00 | 0.01 | ±(2% of setting +2counts) |
Ramp Time, second | 0.1 - 999.9 | 0.1 | ±(0.1% +0.05sec) |
Dwell Time, second | 0, 0.2 - 999.9 (0=continuous) | 0.1 | |
Arc Detection | 0, 1 - 9 ranges (0=OFF, 9 isthe most sensitivity) | ||
INSULATIONRESISTANCE (7112,7122 ONLY) | |||
Output Rating | 1KVDC/1000MΩ | ||
Output Voltage,KVDC | 0.10 - 1.00 | 0.01 | ±(2% of setting +3V) |
SETTINGS | |||
Hi-Limit Resistance,MΩ | 0, 1 - 1000(0=OFF) | 1 | ±(3% of setting+2counts)at >500VDC |
Lo-Limit Resistance,MΩ | 1 - 1000 | 1 | ±(7% of setting +2counts)at<500VDC |
Delay Time,second | 0, 0.5 - 999.9 (0=continuous) | 0.1 | ±(0.1% + 0.05sec) |
MEASUREMENT | |||
AC/DC Voltage, KV | 0 - 6.00 | 0.01 | ±(1.5% of reading +1count) |
DC Voltage, KV (IRonly) | 0.10 - 1.00 | 0.01 | ±(1.5% of reading +3V) |
AC Current, mA | 0.10 - 12.00 | 0.01 | ±(2% of reading +2counts) |
DC Current, mA | 0.02 - 5.00 | 0.01 | ±(2% of reading +2counts) |
Resistance, MΩ | 1 - 1000 (Auto Range) | 0.001 | ±(3% of reading+2counts) at > 500VDC ±(7% of reading +2counts) at <500VDC |
0.01 0.1 | |||
GENERAL | |||
Input Voltage AC | 115/230Vac±15%, 50/60Hz ± 5%,Fuse 3.15A Fast | ||
PLC Remote Control | Input : Test ,Reset | ||
Output : Pass , Fail ,Processing | |||
Memory | 5 Sets Store/Recall of eachMemory, 4 Test Mode Selectable (W, I, W~I, I~W Only 7112, 7122) | ||
Display | 16×2 LCD with backlight | ||
Key Lock | To prevent unauthorizedalteration of the test Parameters | ||
Calibration | Build-in software and externalcalibrated meters | ||
Environment | 0-40℃, 20-80%RH | ||
Dimension/NetWeight | 280mm(W)×89mm(H)×370mm(D)/9Kg | ||
STANDARDACCESSORIES | |||
Power Cord(10A) | ×1 | ||
Fuses | ×3 (Including a spare containedin the fuse holder) | ||
Hipot Test Lead,1.5m(1101) | ×1 | ||
Hipot Return Lead,1.8m(1102) | ×1 |