43pd motor cam switch is equipment to supply electric voltage for control to protection relay, meter ,control |
| |
|
power voltage, etc. due to automatic transference of bus in accordance with connection state of 2nd voltage |
| |
|
of bus p.t in substation double bus structure. 43pd moter cam switch protects occurring malfunction |
| |
|
of equipment in case of manual transference of 2nd voltage. |
| |
this equipment applies for auto-control and scada of efficient application of total protection control system. |
|
| |
|
* applying place of protection relay * - protection panel for t/l railway line) - protection panel for bus) - protection panel for u.f.r) - system voltage of requiring transference of p.t) - protection panel for m.tr 154/23kv) | | |
| |
|
|
| |
|
| contact rating |
250v, 20a |
| maximum rating voltage |
600v |
| dc open-close volume |
dc 125v, 20a (50ms) |
| control power voltage |
dc 125v (range of using voltage : dc94v ~ dc 156v) |
| operating electric current |
below 1.0a |
| transference speed |
after inputting external signal, bus is changed a -> b or b ->a transference time of p.t voltage perfectly is within 2.5sec. in case of supplying rating control voltage dc 125v |
| time of transference current |
after operating switch, bus is changed a -> b or b ->a transference time of no p.t voltage perfectly is within 2.5sec. in case of supplying rating control voltage dc 125v |
| insulation resistance |
above 50m Ω |
| mechanical life time |
above 200,000 times (after operating 1 time, equipment is stopped 5 seconds) | | |
| |
|
|
| |
|
  |
|
manual control | |
 |
|
in case of field test or manual operation requested, pull the handle at pull-out position (manual |
| |
|
operation position) then enable to operate manually |
 |
|
enable to do manual control regardless of contact position of related aux-s/w for remote signal |
 |
|
lighting green led lamp using for indicating manual operating position) |
 |
|
pushing the handle forward at pull-in position (automatic operating position) then led lamp is |
| |
|
changed to red lighting and operated as automatic control | |
| |
  |
|
automatic control | |
 |
|
using it connected with bus aux-s/w contact as below 43pd connection diagram (drawing1) |
 |
|
when bus aux-s/w is transferred then transferred automatically to (a-b bus) appropriate bus(b bus) |
 |
|
unable to operate at bridge position where bus aux-s/w putted into simultaneously and enable to |
| |
|
operate as bus aux-s/w transference completed. |
 |
|
operated automatically only at pull-in position (automatic operating position) pushing front handle forward | |
| |
  |
|
remote control | |
 |
|
using contact of remote control after connecting as below 43pd connection diagram (drawing2) |
 |
|
remote control signal uses three contacts such as a-bus, b-bus, off) |
 |
|
enable to operate at automatic control position (pull-in position) and unable to operate at manual |
| |
|
control position (pull-out position). | |
| |
  |
|
automatic/remote control | |
 |
|
using it connected as below 43pd connection diagram (drawing3)) |
 |
|
motion form of automatic control is same as motion form of remote control) | |
| |
  |
|
built-in remote control method | |
 |
|
pull in the cam switch handle then supply control power voltage to 19 and 20 terminal. at this moment, |
| |
|
check whether green color of led is changed to red color of led pushing handle out after lighting |
| |
|
confirmed) |
 |
|
check remote control pushing handle in center as off position) |
 |
|
check whether the switch handle moves into b-bus when supplying dc+ to no.5 terminal block of cam |
| |
|
switch) |
 |
|
check whether the switch handle moves into a-bus when supplying dc+ to no.7 terminal of cam switch) |
 |
|
check whether the switch handle moves into center position (off) when supplying dc+ to no.9 |
| |
|
terminal of cam switch. | | | |
| |
|
|
| |
|
 |
|
|
|
|
|
|
 |
|
ys ft-1 | |
|
|
|
|
|
| | |
| |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| |
¡ø note |
| |
1. contact composition of dc lock is possible to be different according to 43pd model |
| |
2. 43pd contact composition is basic contact composition |
| |
3. it is able to operate manual control and field test only in case of pulling front handle out | | |